About the UPS Runtime Calculator
How long a UPS will run your load, from battery capacity, voltage and inverter efficiency.
Also known as: ups backup time, how long will ups last, inverter runtime calculator, battery backup time.
How to use this calculator
- Enter battery capacity, battery voltage, load, inverter efficiency and the other fields.
- The result updates instantly as you type — press Calculate (or Enter) at any time.
- Review the breakdown shown under the main result.
- Use Copy result or Share to save the answer or send a link with your inputs.
Formula
runtime = Ah × V × DoD × efficiency ÷ load
Worked example
Using the values pre-filled in the calculator above:
- Battery capacity = 100 Ah
- Battery voltage = 24 V
- Load = 500 W
- Inverter efficiency = 85 %
- Usable depth of discharge = 50 %
- Power factor = 1
the calculator returns:
- Runtime: 2 h 2 min
- Decimal hours: 2.04
- Usable energy: 1.02 kWh
- Battery total energy: 2.4 kWh